Do It Yourself SQM-LE Weather Proof Enclosure
![]() |
Recently I purchased a Sky
Quality Meter (SQM) from the folks at Unihedron.
The SQM is used to measure the sky darkness. The model I purchased is a
lensed meter (SQM-LE) that measures a 20° light cone of the sky and outputs it in Magnitudes per Square
Arc Second (MPSAS) and Nake Eye Limiting Magnitudes (NELM). The
reason the LE model of the meter was chosen is it is accessible via an Ethernet cable. This
allows remote measurements.
But in order for the SQM-LE to work it needs to
be outside. The only problem is the manufacturer didn't enclose it in
a weather proof case. They also didn't provide any way to mount it. Since
my observatory is remotely controlled, the SQM-LE needs to be permanently
mounted, so the above two issues were a real problem. |
![]() |
|
The 2 other main pieces that make up the rest of the
cover: The assembled cover is shown
below. Since the SQM-LE is always on and enclosed it runs warm. The
internal temperature sensor which is mounted just below the light sensor
indicates the internal temperature is about 20
degrees warmer than the ambient outside temperature. This is OK in the winter as
it will help melt any snow that falls on the cover. |
![]() |
|
The enclosure for the SQM-LE is shown here
assembled (minus the vent holes). It is important the to point out that the SQM-LE
needs to be recalibrated when a additional covering is placed over the
factory cover, or if the factory cover is replaced.
The calibration is done by changing the factory Light Calibration Offset value. The factory calibration info is provided on a data sheet that is included with each meter (don't lose it). The amount that the number needs to change is dependent on the properties of the new cover. To get that number requires measuring the meter with the original factory cover in place before any modifications are made, and then again with the new cover installed. The key is the same light source has to be used so the variation in the readings is related to only the covers and not a change in lighting. A Extech 401025 light meter was used to insure the light used before and after the modification was the exactly the same. The plastic cover I used only decreased the light going to the SQM-LE by .04 MPSAS. The folks at Unihedron provide a Java Script that allows the user to change the calibration value. As you can see from the screen copy below the jSQM program allows the user to view and change a number of parameters. |
![]() |
![]() |
|
The finished unit was mounted on the bottom right side of the 120 watt solar panel. The solar panel supplies no power to the SQM-LE. The SQM-LE gets it 5 vdc power from the included AC adapter that is plugged into a weather proof outlet on the outside of the observatory. The original placement of the SQM-LE shown above partially obstructed the solar panel as seen by the shadow. After this picture was taken the SQM-LE's mounting position was changed in order to reduce the shadowing of the solar panel. |
![]() |
|
The bracket that holds the SQM-LE is attached to the back of solar panel support bracket by a single stainless steel screw. The Ethernet and power cables are also tied off here. |
The
SQM-LE is mounted to its support bracket by means of hose clamp.
The support bracket and hose clamp were off the shelf items purchase from the local Sears hardware store. |
![]() |
|
The SQM-LE is tilted at a slight angle to help the water roll off when it rains. The top and bottom sections can be easily be separated if the unit requires service. |
|
|
This view shows
the current mounting position of the meter as well as the vent holes. An additional
hose clamp was added to the existing one so the SQM to be attached to the
bracket closer to the top. This lowered the SQM so the shadow it cast on the
solar panel were greatly reduced.
The vent holes are drilled upward at a 45° angle in order to prevent water from entering the enclosure. In the image above the vents are closed. They can be opened by twisting the lower section counter-clockwise about 1/2 inch until the inner and outer holes are aligned. A screen behind the inner holes prevent bugs or debris from getting inside. (The IP address of the unit is printed on the top.) |
Click on the above drawing for a larger version |
go
to the JATObservatory
Home page
Updated 10/23/2009- Please report broken links webmaster@jatobservatory.org